Product details
The Honeywell Sensepoint XCD is a stationary gas detector designed for industrial hazardous environments, capable of continuous monitoring of combustible gases, toxic gases, and oxygen, suitable for potentially explosive indoor and outdoor environments. Operators can set parameters via the LCD display and magnetic rod switches without opening the lid, enabling single-person maintenance-free maintenance and reducing routine maintenance time and costs.
Product features
- Multiple sensor versions are available: combustible gases (catalytic combustion or infrared), toxic gases, and oxygen
- Suitable for new construction and renovation projects, suitable for both indoor and outdoor installation
- Stainless steel or aluminum alloy explosion-proof housing is available, with a standard protection rating of IP66
- Three-color backlit LCD: green is normal, yellow flashes fault/warning, red flashes alarm, making it clear from a distance
- Magnetic rods are designed without opening the lid, automatically suppressing output during maintenance to reduce false alarms
- 4-20mA output (input current/pull current optional), standard with 2 programmable alarm relays and 1 fault relay, optional MODBUS
- Plug-in sensor modules can be installed locally or remotely, with a maximum remote distance of about 30 meters
- Smart sensor technology with excellent performance, precision, and reliability; Supports infrared sensing technology
Main technical parameters
- Power supply: 12–32 VDC (nominal 24 VDC)
- Maximum power consumption: Electrochemical/infrared about 3.7 W, catalytic combustion about 4.9 W; A maximum impulse current of 24 VDC is about 800 mA
- Output: 4-20mA (sink/source) RS485 MODBUS RTU (optional)
- Relay: 3×5 A @ 250 VAC, normally open/normally closed, alarm/fault programmable
- Housing material: epoxy-sprayed aluminum alloy ADC12/LM25 or 316 stainless steel; Sensor: 316 stainless steel
- Weight: Aluminum alloy approximately 2.0 kg; Stainless steel is about 4.0–5.0 kg
- Installation: integrated mounting plate, 4×M8 mounting holes; Optional horizontal/vertical pipe mounting kit (pipe diameter approximately 1.5–3 inches)
- Cable inlet: UL/c UL version 2×3/4 NPT; ATEX/IECEx version 2×M20
- Protection rating: IP66 (EN60529)
- Certified temperature range: -40°C to 65°C
Capable of detecting gases and typical ranges
- Combustible gases / methane / propane: 20–100% LEL (about 10% LEL in steps)
- Carbon dioxide: up to about 2% Vol
- Oxygen: 25.0% Vol
- Hydrogen sulfide: 10–100 ppm (default about 50 ppm)
- Carbon monoxide: 100–1000 ppm (default about 300 ppm)
- Hydrogen: 1000 ppm
- Nitrogen dioxide: 10–50 ppm (default about 10 ppm)
Certification and compliance
- Complies with UL, INMETRO, ATEX, IECEx, CSA, KTL, PA, GB, CCCF, and other relevant standards
- Suitable for hazardous areas such as Class I Division 1 / Division 2 (according to specific certification model)
Genuine product guarantee, special invoice available, one-year warranty, support for Beijing agency inspection and corporate transfers. Welcome to inquire about model selection and quotation.
Typical applications
- Combustible and toxic gas monitoring for refineries, petrochemical, and natural gas facilities
- Chemical and fine chemical unit areas, tank areas, and loading/unloading areas
- Fixed continuous monitoring for power generation, metallurgy, municipal, and utility engineering
- New projects and existing loop modifications (local or remote sensors)
Ordering code selection guide
- Complete kit ordering codes start with
SPXCDHousing material (AL Aluminum Alloy / AS 316 Stainless Steel), certification and entry (ATEX M20 or UL 3/4" NPT), gas sensor code, optional suffixM(Modbus) - Example:
SPXCDALMB1M= ATEX Aluminum Alloy M20 Infrared CO₂ 0–2%VOL Modbus - Transmitters without sensors, installation accessories, replaceable sensors, and spare parts can be ordered separately. See "Ordering Code Selection Reference" on this page for details